Form

Form - Breathing Air Quality Test Record

Document FSSMS-FRM-12Stage 1Revision 4Version 0.3.3

Topic pages open on your jurisdiction, and requirements tables show its line. You can change this on any page.

One record per sample per air source (compressor outlet, mobile fill unit, cascade bank, purchased air bank). Completed by the fill station operator when the sample is drawn and finished when the laboratory certificate returns; filed with the certificate attached in {{Records system}}; reported in the quarterly update. The purity parameters and the sampling triggers are those of the compressed breathing air standard (CSA Z180.1:19); the department samples quarterly, which also meets the emergency services breathing air standard (NFPA 1989, 2019) and the breathing air requirement of the health and safety standard (NFPA 1550, 2024, s. 9.12).

The form

Field Entry
Record number
Air source (compressor serial and location / mobile unit / cascade bank / purchased air lot)
Reason for sample (commissioning / scheduled quarterly / after major overhaul / after extensive repair / after filter change / after alarm or event / purchased air verification)
Date and time sample drawn
Sample drawn by (operator name, training reference)
Sampling method and container ID (laboratory kit reference)
Compressor hours at sampling; last filter change date; CO monitor reading at sampling; CO monitor last calibration date
Laboratory (name, accreditation reference)
Date sent; date certificate received; certificate number
Oxygen, percent by volume (limit 20 to 22) Result: Pass / fail:
Carbon monoxide, ppm (limit 5 or less) Result: Pass / fail:
Carbon dioxide, ppm (limit 500 or less) Result: Pass / fail:
Oil and condensed hydrocarbons, mg/m3 (limit 1 or less) Result: Pass / fail:
Particulates, mg/m3 (limit 1 or less) Result: Pass / fail:
Non-methane volatile hydrocarbons (Table 1 limit) Result: Pass / fail:
Halogenated hydrocarbons (Table 1 limit) Result: Pass / fail:
Methane (Table 1 limit) Result: Pass / fail:
Water vapour or dew point (limit for the lowest service temperature) Result: Pass / fail:
Odour (none objectionable) Result: Pass / fail:
Overall result (all parameters within limits: yes / no)
If any parameter failed: filling stopped (date, time); cylinders quarantined (serials or fill log range); cause found; corrective action number; re-test record number; return to service (date, by)
Notified (program administrator, HSO, JOHSC) with dates
Next scheduled sample due
Reviewed by program administrator (name, date)

Fields

Field Type Required Who completes
Record number Text, unique Yes Program administrator or system
Air source Choice plus identifiers Yes Operator
Reason for sample Single choice Yes Operator
Date and time drawn Date, time Yes Operator
Drawn by Text Yes Operator
Sampling method and container ID Text Yes Operator
Compressor hours; filter change date; CO reading; CO calibration date Number; date; number; date Yes for compressor sources Operator
Laboratory and accreditation Text Yes Operator
Dates sent and received; certificate number Dates; text Yes Operator; program administrator on receipt
Each purity parameter result and pass / fail Number; choice Yes Program administrator from the certificate
Overall result Yes / no Yes Program administrator
Failure actions Text, dates, references Yes if any parameter failed Operator and program administrator; HSO confirms corrective action
Notifications Text with dates Yes if any parameter failed Program administrator
Next sample due Date Yes Program administrator
Reviewed by Name, date Yes Program administrator

Retention. Life of the air source plus five years, with the certificate (05 Document Control and Records). Audit use. The auditor checks the last four records per source for interval, completeness, every parameter within limits, and the failure actions where any result was out of limit.

Jurisdiction requirements

This chapter relies on the following legal requirements, which differ by province and territory. Check your jurisdiction’s section on each topic page before adopting it.

Topic What to check in your jurisdiction Page
Respiratory Protection, Fit Testing and Breathing Air Which breathing air standard and edition the regulation names, any test interval it sets (the quarterly schedule here is the department’s choice), and the cylinder requalification rules J14 Respiratory Protection, Fit Testing and Breathing Air

References

CSA Group. (2019). CSA Z180.1:19, Compressed breathing air and systems (6th ed.). https://www.csagroup.org/store/product/CSA%20Z180.1:19/

National Fire Protection Association. (2019). NFPA 1989, Standard on breathing air quality for emergency services respiratory protection (last standalone edition; scheduled to consolidate into NFPA 1985). https://www.nfpa.org/codes-and-standards/nfpa-1989-standard-development/1989

National Fire Protection Association. (2024). NFPA 1550, Standard for emergency responder health and safety (consolidates NFPA 1500, 1521 and 1561). https://www.nfpa.org/codes-and-standards/nfpa-1550-standard-development/1550

© 2026 The Human Factor · Licensed under CC BY-NC-SA 4.0 with the Adopting Agency Grant

General information only, not legal, medical or other professional advice. Verify every requirement against the current official text of the law, standards and manufacturer instructions that apply to you. Obtain your own legal review and consult your joint health and safety committee before adopting anything. You adopt, adapt, implement and rely on this material entirely at your own risk and on your own responsibility. Full terms: Terms of Use, thehumanfactor.ca.